(Why is the value 30mA in the differential interrupter, and how did we find it…??)

(Why is the value 30mA in the differential cutter, and how did we find it…??)

 Today, God willing, we will talk about an important topic, which is the value of the electrical sensitivity of the differential cutter…

 A question arises, which is why we put a differential cutter with a sensitivity value of 30mA, and how did we find this value…?? which equals 0,03A

 It is known that when we put an electrical panel, we put a differential separator with a sensitivity of 300mA and a differential circuit with a sensitivity of 30mA, and that the average human resistance in a dry medium is 1660 ohms, according to scientific studies, and that what constitutes a danger or kills a person is the current (umbar) and not the tension (voltage). According to studies, it has always been found that the value of 50 volts In a dry environment, it can pose a danger to humans…

 Now we have two things:

 The average human resistance in a dry medium is 1660 ohms, and the voltage that can pose a danger to humans is 50 volts…

 From here we do a simple calculation:

 We divide the voltage that poses a danger to humans in a dry medium of 50 volts by the average human resistance in a dry medium of 1660 ohms…

 We get a value of 30mA

 50v ÷ 1660 = 0.031 = 30ma = 0.03a

 So the value of 30 ma came through these calculations

 There is a note that when we are in a wet, floating, swimming pool or bath, for example, this value changes and becomes 10ma

 Another question arises, which is why do we put a differential separator diférrentiel 300ma and an intérupteure diférrentiel 30ma and why don’t we put them in the same value…??

 The answer is:

 If we put them in the same value, we cannot achieve electrical selectivity la sélectivité électrique, in order to achieve electrical sensitivity, the sensitivity of the differential separator must be greater than the sensitivity of the differential cutter so that they do not separate the current with each other …